Accurate measurement of kWh, kvarh, & kVAh
Maximum demand registration of kW, kvar & kVA
Instrumentation of voltage, current, power, frequency & power factor
Time of Use (TOU) control with fexible programming for up-to 8 tarifs
2 load profles with recording of up-to 180 days at 30’ interval
4 event logs with configurable power quality or tampering events
High quality 11-digit LCD display with large characters & backlight
– Internal real-time clock (RTC) with super capacitor and backup battery
– Supports DLMS, IEC 62056-21, or MODBUS communication protocols
– Encapsulation type meter casing design for reliability and security
– Replaceable backup battery for meter reading without power
Product Description
Technical Specifications
P2000-D
ELECTRICAL | MEASUREMENT & INSTRUMENTATION | ||
Connection Type | Direct connected (Whole current) | Energy | Total & per phase import/export kWh, kvarh, kVAh; Absolute or net metering |
Measurement Modes | 3-phase 4-wire 3-element | Maximum Demand | Total & per phase import/export kW, kvar, kVA |
Accuracy Class | Class 1.0 | Automatic Billing Data Recording / MD Reset |
Date & Time Programmable |
Rated Voltage | 240/415V | Instantaneous Values | Current, Voltage, Power, Average Demand, Power factor, Phase Angles and Frequency |
Rated Current | 10 (100) A | ||
Starting Current | < 0.1% I | ||
Rated Frequency | 50 Hz | ||
Power Consumption Voltage Circuit Current Circuit |
< 1W, < 2.5VA per Phase < 0.1VA |
||
MECHANICAL | LOAD PROFILE | ||
Dimensions | 285 mm x 200 mm x 94mm | Load Profile | 2 configurable load profiles |
Weight | 2 kg (approximately) | Channels | 16 configurable channels |
Insulation | Protective Class II | Available Data | All energy, demand, & instrumentation data (see above for details) |
Ingress Protection | IP54 | Integration Period | 15 to 60 minutes configurable |
Case / Terminal Cover | High Quality Polycarbonate | Memory Space | Up-to 180 days with 30’ interval |
Terminal Block | Flame-Retardant Polycarbonate | Data Retention | 25 Years |
ENVIRONMENT | EVENT LOG | ||
Working Temp. | -25°C to +75°C | Event Log | 5 configurable event logs |
Storage Temp. | -40°C to +85°C | Trigger Events | Power break, phase failure, phase voltage loss, voltage over, voltage under, current loss, current over, current imbalance, reverse current flow, reverse power, reverse energy, phase reverse, overload, terminal cover open, meter top cover open |
Humidity | 0 – 95% non condensing | Data Recording at Event | 8 configurable channels of energy, demand, & instrumentation data recording |
Insulation | 0 – 95% non condensing | Program Record | Last 100 program records |
Fast Transient Burst | 4kV | ||
Static Discharge | 8kV Contact / 15kV Air Discharge | ||
Impulse Voltage | 12kV, 1.2/50 μs pulse | ||
AC Voltage | 4kV, 50Hz | ||
REAL-TIME CLOCK | TIME OF USE (TOU) CONTROL | ||
Accuracy | < 0.5 seconds / 24 hours | Number of Tariffs | 4 tariffs, or 8 tariffs (optional) |
Backup Battery | Lithium Battery (20 years life) | Daily Profiles | 12 daily profiles, 14 tariff slots |
Backup Time | ≥ 15 years without power | Week Tables/Seasons | 12 week tables, 12 seasons |
Clock Synchronization | Local or remote via AMR | Holidays | 120 special days (up-to 250) |
DISPLAY | PREPAYMENT & LOAD CONTROL | ||
LCD Display | 2 line, 8-digit LCD display | Prepayment Feature | STS certified via token or smart card |
Display Mode | Automatic, Push Button, Test | User -Friendly Prepayment Modes |
Friendly hours/days, emergency credit and vital necessity power |
Display Item | 200 configurable display items | Load Control | Scheduled / on-demand or event triggered load control |
Internal Contactor | 100A internal contactor | ||
INPUT & OUTPUT | |||
Electric Pulse I/O | 4 Programmable Ports | ||
Test Pulse Output | 400 – 8000 imp/kWh, kvarh | ||
LED Pulse Output | 400 – 8000 imp/kWh | ||
Pulse Constant | Programmable | ||
Auxiliary Power | 110V – 240V (optional) |