•Measurement of active energy (bidirectional), reactive energy (in 4-quadrants) and maximum demand
• Accuracy class 1.0 (B) or 0.5s (C)
• Measurement in two channels (on phase and neutral lines)
• Single or Multi -tariff (up to 6 tariff s)
• Internal real ti me clock
• Load and billing profi les, instantaneous values
• Extended anti -tamper features
• Event logbook (power outage, power over-limit, reverse current flow,
influence of magnetic field, opening of meter cover, opening of terminal cover,
clock setting, parameter change, internal error, firmware update)
• Optical and electrical communication interfaces in accordance with IEC 62056-21 and/or DLMS/COSEM
• Internal communication modules (PLC modem, USB host, wireless or wired MBus, RS485, Ethernet), powering of external modem
• High-level security (encryption and authentication)
• Internal relay for user disconnection
• Power quality monitoring (over-voltage, under-voltage, over-current)
• Measurement of Total Harmonic Distortion (THD)
• Registration of line and transformer losses on the basis of I2h and U2h
measurements

Product Description

RATINGS
System Three-phase 4-wire or 3-wire
Accuracy class:
• For active energy
• For active energy, CT only
• For reactive energy
• class 1.0 (IEC 62053-21), class B (EN 50470-3)
• class 0.5s (IEC 62053-22), class C (EN50470-3)
• class 2.0 (IEC 62053-23)
Reference voltage, V:
• 4-wire networks
• Multirange
• 3-wire networks
• 3×220/380; 3×230/400; 3×240/415; 3×57,7/100; 3×63,5/110; 3×69,2/120; 3×120/208; 3×127/220
• 3×57,7/100…230/400
• 3×100; 3×110; 3×120; 3×220; 3×230
Reference (maximum) current, A:
• Directly connected
• CT operated
• 5(60); 5(80); 5(100); 5(120); 10(60); 10(80); 10(100);
• 1(1.25); 1(6); 5(6.25); 5(10);
Current threshold 0.4% I (0.1% I if CT operated)
Reference Frequency, f 50 or 60 Hz
Meter constant, imp/kWh, imp/kVArh 1…19999 (direct), 1…60000 (CT operated)
Power consumption per phase:
• In voltage circuit
• In current circuit
• < 0.5W < 1.0 VA
• < 0.05 VA (< 0.5 VA if CT operated)
Temperature ranges:
• Meter operating
• Meter storage
• -40°C…+70°C
• -40°C…+70°C
INTERNAL REAL-TIME CLOCK
Accuracy < 0.5 s/24h (T = 23°C)
Backup power supply Li-ion battery and/or Super-Cap
Li-ion battery  Changeable on operating meter
Operation duration using only backup:
• Li-ion battery
• Super-Cap
• > 10 years
• up to 7 days
CASE & DIMENSIONS
Case UV stabilized polycarbonate
Insulation Protective class II
Protection Class IP51
Dimensions, mm 260 x 175 x 80